Illinois Bids > Bid Detail
MODULAR WATER CHILLER
Agency: | |
---|---|
Level of Government: | Federal |
Category: |
|
Opps ID: | NBD00159457586117196 |
Posted Date: | Oct 10, 2023 |
Due Date: | Oct 17, 2023 |
Source: | https://sam.gov/opp/aa0ae81ba2... |
Follow
Active
Contract Opportunity
Notice ID
RFQ349798_BLN
Related Notice
Department/Ind. Agency
ENERGY, DEPARTMENT OF
Sub-tier
ENERGY, DEPARTMENT OF
Office
FERMILAB - DOE CONTRACTOR
Looking for contract opportunity help?
Procurement Technical Assistance Centers (PTACs) are an official government contracting resource for small businesses. Find your local PTAC (opens in new window) for free government expertise related to contract opportunities.
- Contract Opportunity Type: Solicitation (Original)
- All Dates/Times are: (UTC-05:00) CENTRAL STANDARD TIME, CHICAGO, USA
- Original Published Date: Oct 10, 2023 02:11 pm CDT
- Original Date Offers Due: Oct 17, 2023 04:00 pm CDT
- Inactive Policy: 15 days after date offers due
- Original Inactive Date: Nov 01, 2023
-
Initiative:
- None
- Original Set Aside: Partial Small Business Set-Aside (FAR 19.5)
- Product Service Code: 4120 - AIR CONDITIONING EQUIPMENT
-
NAICS Code:
- 333415 - Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing
-
Place of Performance:
Batavia , IL 60510USA
FERMILAB REQUESTS YOUR FIRM FIXED PRICE QUOTE FOR THE FOLLOWING MODULAR WATER CHILLER:
1 EACH MODULAR WATER CHILLIER PER SPECIFICATIONS BELOW:
- A modular water-cooled water chiller.
- Each module shall include two independent cooling circuits. Each circuit must provide a minimum of 28 kW (96,000 Btu/h or 8 tons) cooling capacity at 60 degrees F, for a total of at least 56 kW per 2-circuit module.
- We will initially purchase one module. The system must be expandable with the addition of more modules up to at least 200 kW total capacity.
- Shall meet ASHRAE 15 code requirements. A certification shall be provided by the vendor stating that the unit is code compliant.
- Power requirements: 480 Volts/ 3-phase power, 60 Hz
- The system shall be provided with a control system capable of monitoring the correct functioning of each chiller circuit and generating alarms for out of normal conditions. The chiller controller must be capable of interfacing with an external control system using a Modbus TCP/IP interface.
- Variable speed or digital scroll compressor type is preferred.
- Brazed plate heat exchangers are preferred type for both condenser and evaporator.
SARC AND PUR466 MUST BE SUBMITTED WITH ALL PROPOSALS.
Attachments/Links
Contracting Office Address
- Kirk Rd. & Pine St.
- Batavia , IL 60510
- USA
Primary Point of Contact
- Brian Nielsen
- bnielsen@fnal.gov
- Phone Number 6308403554
Secondary Point of Contact
- Oct 10, 2023 02:11 pm CDTSolicitation (Original)
TRY FOR FREE
Not a USAOPPS Member Yet?
Get unlimited access to thousands of active local, state and federal government bids and awards in All 50 States.